ERCES Codes

ERCES protect your residents and tenants

NFPA 1225 & Public Safety Radio Coverage Requirements

What Is NFPA 1225?

NFPA 1225 is the national standard that governs Emergency Responder Communication Enhancement Systems (ERCES)—the in-building radio systems that allow firefighters, police, and EMS personnel to communicate clearly inside structures where radio signals are otherwise blocked by concrete, steel, or energy-efficient glass.

Adopted by jurisdictions throughout California and across the U.S., NFPA 1225 defines the performance, testing, and maintenance criteria for reliable public-safety radio coverage inside buildings.

When an ERCES Is Required

Most cities and counties reference IFC Section 510 or California Fire Code 510.
These codes determine when a system is required.
Once radio coverage is mandated, NFPA 1225 specifies how the system must be designed, powered, supervised, and tested to meet the Authority Having Jurisdiction (AHJ) requirements.

Typical triggers include:

  • New construction or major renovations
  • High-rise or underground structures
  • Buildings with known dead zones or low radio penetration
  • Fire Marshal-requested coverage verification tests

Core Performance Requirements

  • Coverage Area:
    • 90 % of each floor must meet the minimum signal level.
    • 99 % coverage required in critical areas—stairwells, fire command centers, fire pump rooms, and exit passageways.
  • Signal Strength:
    • Reliable two-way (uplink & downlink) communication at the prescribed signal levels, typically around −95 dBm or better.
  • Audio Quality:
    • Minimum Delivered Audio Quality (DAQ) 3.0 ensures intelligible voice transmission.
  • Testing Method:
    • Grid-based acceptance testing verifies both directions of communication prior to approval and during annual re-certification.

System Components

A compliant NFPA 1225 ERCES includes:

  • Donor Antenna: Roof-mounted, receives and transmits to the public-safety radio network.
  • Bi-Directional Amplifier (BDA): Listed for public-safety use and tuned to the jurisdiction’s licensed frequencies.
  • Coaxial or Radiating Cable Network: Distributes signals to remote antennas throughout the building.
  • Monitoring & Alarms: Interfaces with the building’s fire alarm control panel to report any faults, power loss, or oscillation.
  • Battery Backup: Provides 12–24 hours of standby power during an outage, depending on local requirements.

Power & Supervision

NFPA 1225 mandates:

  • A dedicated electrical circuit for the ERCES equipment.
  • Secondary power via supervised batteries or an equivalent energy source.
  • NEMA-rated enclosures appropriate for the installation environment (often NEMA 4 or 4X).
  • Automatic trouble reporting to the building’s fire alarm system for any failure or fault condition.

System Survivability

Critical pathways—such as riser coax, backbone cables, and power circuits—must remain functional during a fire.
NFPA 1225 allows several protection methods:

  • 2-hour fire-rated cable (CI/MI or “Dragonskin”)
  • Cable in 2-hour rated conduit or shaft
  • Alternative equivalent fire-resistive assemblies approved by the AHJ

Acceptance Testing & Documentation

Prior to final approval, the ERCES must pass a full acceptance test and submittal package including:

  1. Downlink and uplink coverage test results
  2. Alarm, power, and oscillation verification
  3. Battery discharge test
  4. As-built drawings and antenna layout maps
  5. Manufacturer data sheets and equipment listings

After occupancy, NFPA 1225 requires annual inspection and testing to verify continued compliance and system reliability.

Why NFPA 1225 Compliance Matters

In an emergency, reliable radio coverage can save lives.
An ERCES designed and maintained to NFPA 1225 standards ensures:

  • Clear communication for first responders in every area of the building
  • Rapid coordination of emergency efforts
  • Ongoing protection for building occupants and emergency personnel

Partner with In-Building Wireless Solutions

In-Building Wireless Solutions LLC designs, installs, and maintains NFPA 1225-compliant ERCES / public-safety DAS systems across Northern California.
We work directly with fire departments, general contractors, and electrical engineers to ensure every project passes coverage testing and AHJ inspection the first time.

Call 415-738-6895 or visit www.in-buildingwireless.com for consultation, design, or compliance testing services.

Have Questions?

We have answers. Please fill out the form on this page, and someone from our team will be in touch shortly. Thanks for your interest! →

Yes, Please Send Me More Information

Education Center

How Cellular DAS Boosts Property Value and Tenant Satisfaction

In today’s connected world, reliable cellular coverage inside a building is no longer a luxury—it’s an expectation. Tenants (or residents), guests, and staff all rely on strong mobile service for communication, safety, and productivity. Yet many commercial and...

IBWS – Our Approach

This blog has primarily focused on the issues and details of ERCES in California. This is an admittedly technical subject that those in the industry who read this probably don’t have friends and family eager to discuss with them. So, in the interests of taking a break...

NFPA 72’s 2025 Edition and ERCES

Effective January 1, 2026, the 2025 Edition of NFPA 72 (National Fire Alarm and Signaling Code) will take effect in California.  Per NFPA’s website, the 2025 edition features several revisions and additions to the standard, including the following (verbatim): Expanded...

Who are the Stakeholders in an ERCES?

Who does what in an Emergency Responder Communication Enhancement System (ERCES)? The answer: Several organizations are typically involved in designing, installing, and maintaining an ERCES. Each has a distinct role. This matrix, courtesy of the Puget Sound Emergency...